Have you ever wondered a Data center that adapts to your needs?

Whatever the vertical, type or size, every company has a common and urgent need: to store data in a stable and secure way. Indeed, in the last years, data has grown in importance day after day, becoming a real business assets and as such, they need to be safeguarded at best.

The space, power, and connectivity you need, and the agile, personalized service you deserve.

Server cabinets are installed on a raised floor and organized to create an isolated cold passage that receive fresh flows from below through a single air volume. In this way warm and cold water cannot mix ensuring great energy savings.

bancadati_datacenter
bancadati_datacenter
bancadati_datacenter

The Data center cooling system uses ground water collected through two redundant wells with a concession of 1.800 liters/minute, providing water between 12°C and 15°C to the server-cooling machines.  Additionally an evaporative tower with adiabatic process of 1.500kWf gurantees the continuity of service in case of well breakdown or maintenance.

An air/water heat pump produces chilled water at 9°C , allowing HIROSS cabinets to cool up the UPS, the electric panel and the electric transformer rooms when necessary. In case of breakdown split refirgerators of 15 kWf are used in the UPS rooms.

bancadati_datacenter
bancadati_datacenter
bancadati_datacenter

Secure. Private. Stable

Choose the Data center the will give you the basis to start your Digital Transformation

Bancadati is provided with a double sensor detection system and an automatic extinction system with 42 tanks of Inergen gas, that is totally harmless for both people and machines.

The double detection sensors can exactly identify the area where the extinction is requires and in few seconds the system distributes the gas with a modulated pressure of 50 bar. During this operation the cooling system keep on working ensuring the temperature set-point.

bancadati_datacenter
bancadati_datacenter

Electricity supply is guaranteed by a medium voltage input with a substration of 4 transformers 0f 1.000 kVA each one. 4 main electrical panel distribute energy to Bancadati on redundant and separate lined that follow different paths.

The secondary distribution electrical panels bring power to the server rooms where each rack receive redundant power from 2 distinct and completely separated lines.

In case of power failure, 2 groups composed of 3 UPS of 300 kVa each, guarantee power supply continuity to the Data center for 10 minutes at full load. Within one minute from the power failure, diesel engine-generators of 900 kVa each come into operation providing the necessary energy for the whole Data center.